An alternative proposal for HVDC transmission systems using 24-pulse AC/DC converters based on three-winding non-conventional transformers
| dc.contributor.author | OGOULOLA, christel enock ghislain | |
| dc.contributor.author | Rezek, Angelo José Junqueira | |
| dc.contributor.author | FIFATIN, François-Xavier | |
| dc.contributor.author | Silva, Vinicius Zimmermann | |
| dc.contributor.author | Gonzatti, Robson Bauwelz | |
| dc.contributor.author | de Oliveira, José Carlos | |
| dc.contributor.author | Di Lorenzo Correa, Rafael | |
| dc.date.accessioned | 2026-06-02T16:06:57Z | |
| dc.date.available | 2026-06-02T16:06:57Z | |
| dc.date.issued | 2020 | |
| dc.description.abstract | In order to promote savings on installed filters in traditional HVDC transmission systems, and thus provide a less polluted power quality, this paper proposes a 24-pulse controlled converter that uses two identical three-phase three-winding special transformers, as well as four thyristor-controlled 6-pulse AC/DC converters connected in series. The configuration of the two transformers, and the necessary tap calculations are presented in order to achieve the 7.5° phase lag required to obtain the 24-pulse converter system. An analysis of the performance indices (power factor and Total Harmonic Distortion – THD) of both HVDC systems (traditional 12-pulse and the proposed 24-pulse) is performed and the results show improvements in the indices when using the proposed 24-pulse system. Simulation analysis was performed using Matlab/Simulink software in order to validate the proposed 24-pulse converter for use in HVDC transmission systems, considering the operationality of the proposed system under normal and degraded operating conditions. A laboratory prototype was designed and executed based on transformers with extended delta primary windings to validate the proposed 24-pulse converter in terms of harmonic mitigation and improved power quality. The results confirm the viability and applicability of the proposed converter in HVDC transmission systems. | |
| dc.identifier.doi | 10.1016/j.epsr.2020.106230 | |
| dc.identifier.other | BECDB-12852 | |
| dc.identifier.uri | https://dspace.uac.bj/handle/123456789/11081 | |
| dc.language.iso | fr | |
| dc.relation.ispartof | Electric Power Systems Research (Elsevier) | |
| dc.subject | HVDC systems | |
| dc.subject | Harmonic filter | |
| dc.subject | Harmonic mitigation | |
| dc.subject | Power factor | |
| dc.subject | Special transformers | |
| dc.subject | Total harmonic distortion | |
| dc.title | An alternative proposal for HVDC transmission systems using 24-pulse AC/DC converters based on three-winding non-conventional transformers | |
| dc.type | Article |
Files
Original bundle
1 - 1 of 1
Loading...
- Name:
- 52c313b9f5334f8e0f605025945180c0.pdf
- Size:
- 3.1 MB
- Format:
- Adobe Portable Document Format